Fantech SHR Heat Recovery Ventilator
Suitable for very large residential or small commercial applications, the compact SHR 3205RD comes with access panels on both sides of the unit for installation versatility. The unit is designed for higher static pressure and higher airflow applications.
SHR 3205RD Fresh Air Appliance
- Airflow up to 259 cfm @ 0.4" PS serves 7 bedroom homes
- Doors on 2 sides of the cabinet for access to multiple cores
- External dry contacts for quick connection of remote controls
Application
Suitable for very large residential or small commercial applications, the compact SHR 3205RD comes with access panels on both sides of the unit for installation versatility. The unit is designed for higher static pressure and higher airflow applications.
Voltage | 120 | V |
Frequency | 60 | Hz |
Phase | 1 | ~ |
Rated power | 300 | W |
Current | 2,5 | A |
Airflow high | 259 | cfm |
Static pressure | 0,4 | in.wg |
Certificate | CSA, HVI | |
Weight | 79,4 | lbs. |
Dimension
A | B | C | D | E | Duct Size |
2 1/4 (57) | 27 7/8 (708) | 2 3/4 (70) | 25 1/4 (641) | 20 1/2 (521) | 8 (203) |
Dimensional information is in inches (mm) |
Specs
Fans
Four (4) factory-balanced fans with backward curved blades. Motors come with permanently lubricated, sealed ball-bearings to guarantee long life and maintenance-free operation.
Heat Recovery Core
Two (2) aluminum heat recovery cores covered by a limited lifetime warranty. Core dimensions are 12” x 12” (305 x 305 mm) with a 11.5” (292 mm) depth. Our heat exchangers are designed and manufactured to withstand extreme temperature variations.
Defrost
During the defrost sequence, a motorized damper temporarily blocks the incoming fresh air stream so that the warm air from the house can circulate through the HRV. The exhaust blower shuts down and the supply blower switches into high speed to maximize the effectiveness of the defrost strategy. During this cycle, household odors from the kitchen or bathroom are prevented from entering the home and the unit will not create negative pressure.
Serviceability
Core, filters, fans and drain pan can be easily accessed through latched door. Core conveniently slides out on our new easy glide core guides. 14" (356 mm) of clearance is recommended for removal of core.
Case
24 gauge galvanized steel. Baked power-coated paint for a superior adhesion and resistance.
Insulation
Cabinet is fully insulated with 1” (25 mm) high density expanded polystyrene.
Filters
Two (2) washable electrostatic panel type air filters 11.5” (292mm) x 11.4” (290mm) x 0.125” (3mm).
Controls
External three (3) position (Low/Stand By/Medium) rocker switch that will offer continuous ventilation. Fantech offers a variety of external controls. (see accessories)
Installation
Unit is typically hung by using installation kit supplied with unit. Mounting bolts provided on top four (4) corners of unit.
Warranty
Limited lifetime on aluminum core, 7 year on motors, and 5 year on parts.
Requirements and standards
- Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
- Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
- Complies with the CSA F326 requirements regulating the installation of Heat Recovery Ventilators
- Technical data was obtained from published results of test relating to CSA C439 Standards
- HVI certified